Product Features
Modular Design
Status Indicator
Protect The Circuit
Product Details
Type | T2-DC 2P/3P—- |
Rated voltage (max.continuous a.c.voltage) [ UC ] | 275V DC/1000V DC/1500V DC |
Nominal discharge current (8/20) [ In ] | 20kA |
Maximum discharge current (8/20) [ Imax ] | 40kA |
Voltage protection level [ Up ] | 275V DC:W4.0kV/1000V DC:W4.5kV/1500V DC:W4.5kV |
Follow current extinguishing capability at UC [ If ] | 32A fuse will not be triggered at 2kA 255V |
Response time [ tA] | <25ns |
Max.backup fuse(L) | 200A gL/gG |
Max.backup fuse(L-L’) | 125AgL/gG |
TOV voltage | 355V / 5sec |
Operating temperature range (parallel wiring) [ Tup ] | -40C…+80C |
Operating temperature range (through wiring) [ Tus ] | -40 °C…+60 C |
Cross-sectional area | 35mm2 solid / 50mm2 flexible |
Mounting on | 35mm DIN rail |
Enclosure material | UL94-V0 |
Dimension | 18mm |
Test standards | IEC 61643-1; GB 18802.1; YD/T 1235.1 |
Certification | CE ISO9001 |
Type of remote signalling contact | Switching contact |
Switching capacity a.c | 250V /0.5A |
Switching capacity d.c | 250V/0.1A; 125V/0.2A; 75V/0.5A |
Cross-sectional area for remote signalling contact | Max. 1.5mm2 solid / flexible |
Get A Great Quote For PV Surge Protector
Product FAQ
How does PV Surge Protector work?
When the system has overvoltage due to lightning strikes or other reasons, PV Surge Protector can respond in nanoseconds and introduce overvoltage into the ground for discharge, thereby protecting the equipment.
What should be paid attention to when installing PV Surge Protector?
It should be installed as close to the protected equipment as possible, and the length of the connecting cable should be shortened. When wiring, ensure the polarity is correct and do a good job of waterproof sealing.
What are the grounding requirements of PV Surge Protector?
PV Surge Protector must be reliably grounded, the grounding cable should be as short and thick as possible, and the grounding resistance should meet the requirements of relevant standards.
Can lightning damage be completely avoided by using PV Surge Protector?
PV Surge Protector can greatly reduce the risk of lightning damage, but it cannot be avoided 100%. Other lightning protection measures should also be taken, such as lightning rods, shielding, etc.
How to judge the failure of PV Surge Protector?
Most products have fault indications, such as green lights for normal and red lights for faults. Some also have remote monitoring functions, which can grasp the working status in real time.